Introduction to SAPHIR Controller Programming

Introduction to Saphir Controller Programming

(Beijing Shilin Taike Automation Technology Co., Ltd.)


1. Software Installation

1) Several software commonly used in programming, debugging and maintaining the Sapyr controller:

2) Sapro programming software, necessary functions in the project, writing control programs, IO channel configuration, signal types, etc.

3) Sapro library provides more functional blocks to meet more complex needs, making programming easier and faster.

4) Saphirscope tool software, necessary functions in the project, controller hardware upgrade, program upload, download, data monitoring, etc.

5) JAVA virtual services, auxiliary functions, access to the controller through IE browser, view the controller version, monitor data, with the upgrade of the controller version, the function is gradually strong.

2. Controller hardware upgrade

The Saphir controller's version, software version, supported function blocks, communication modules, etc. are closely related, because the version of the problem may lead to some functions are not supported, the communication card function does not support, so before deciding to install, Please first determine if the hardware version and software version are compatible.

Controller upgrade steps:

1) Disconnect controller power

2) Short the X19 on the ACX32 motherboard

3) Turn on the controller power

4) Disconnect X19 Shorting Links

5) Run the upgrade software, select the upgrade file

6) Perform hardware upgrade file download

7) Observe changes in download progress bar

8) After downloading, restart the controller power


Hardware upgrade

Note: The controller's power supply is best to select the DC 24V, although it supports AC 24V power supply, but in order to avoid interference, the best choice for DC 24V power supply.

3. Related cable production

Programming cable or communication cable production:

Saphir controller programming interface is RJ45 female, the definition of each needle as shown below


RJ45 (male) RS232 (female)

1----------------5

2----------------3

3----------------8

4----------------2

5----------------7

Expansion module wiring production:


2---------------2

3---------------3

5---------------5

7---------------7

8---------------8

Note: slave station ACX42 module address jumper.

4. Saphir programming


1) Support IEE61131 standard

2) Function Block Diagram Programming

3) Online monitoring, easy to debug, can be forced to value

4) Various kinds of communication function blocks, such as M-BUS, LON, MODBUS, etc., programming is convenient

5) Structure is clear, function block can be customized

This entry was posted in on